Zone function settings

You can add, edit, or delete Zone function settings of multiple Zones.
The settings are applied to the selected Zones in the "Bulk Edit Zones."

NOTES:

  • The information set here is saved on the “Zone setting” screen, but it is not saved on the "Bulk Edit Zones" screen.
  • Existing information on the "Zone setting" screen is overridden by the information set on this screen.
  • When the system is in a special state, such as maintenance or operation prohibition, the settings may not be reflected in the indoor unit.
Start/stop the operation of all selected Zones

To start the operation of all indoor units in the selected Zones, select the [ALL START] button (a).

To stop the operation of all indoor units in the selected Zones, select the [ALL STOP] button (b).

Add or edit the Zone function settings
  1. To edit the Zone function settings, skip to step 4.
    To add the Zone function settings, select [+ADD] button (a).
    "Add Zone Functions window" appears.

    • When no Zone function is set
    • When any Zone function is set
  2. Select the functions (b).
    The frames of the selected functions turn blue.

    • Thermal ZFC
      This can be selected when the device with thermal function is registered in the selected Zone.
    • Ventilation ZFC
      This can be selected when the device with ventilation function is registered in the selected Zone.
  3. Select [Save] button (c).
    The selected functions are added, and the window closes.

  4. Edit the Zone function settings.
    Thermal ZFC:
    To change the temperature setting, slide the bar (d).
    To change the operation mode, select (e).
    Ventilation ZFC:
    To change the airflow volume, select (f).
    To change the temperature setting, slide the bar (g).
    To change the operation mode, select (h).

NOTES:

  • For Auto mode, if all indoor units in the selected Zone are Single Setpoint Auto, the Thermal ZFC for Single is displayed.
  • For Auto mode, if all indoor units in the selected Zone are Dual Setpoint Auto or Single and Dual are mixed, the Thermal ZFC for dual is displayed.  
  • When the temperature setting range is restricted by “Temperature Limit” setting of the indoor unit registered in Zone, the temperature setpoint setting range that can be set in "Zone Functions" is also restricted in the same way.

  • When two or more indoor units are registered in Zone, the temperature setpoint setting range by "Zone functions" is restricted by the smallest value of the upper temperature limit and the largest value of the lower temperature limit set by each indoor unit in "Temperature Limit".

Delete the Zone function settings
  1. Select the Menu button (a) of the function to be deleted.
  2. Select [REMOVE] from the Link button.
    A confirmation message appears.
  3. Select the button (c).
    The function is removed, and the window closes.


NOTE: When the operation mode is set while its setting is limited, it is not reflected in the indoor unit even if saved.
If the changed setting is not reflected in the operation mode, confirm that the operation mode is active.

About Dual Setpoint Auto operation (Dual Setpoint)

  • Dual Setpoint Auto:
    Set the set temperature for cooling and the set temperature for heating separately.
    During the Dual Setpoint Auto mode operation, when the room temperature exceeds the set temperature for cooling, the cooling operation is performed, and when the room temperature falls below the set temperature for heating, the heating operation is performed.
    (It can be used only when the setting of the indoor unit compatible with this function is valid.)
  • The settable temperature range is different for each operation mode.
    Settable temperature range
    Cool/Dry 18°C to 30°C (64°F to 88°F) or 20°C to 30°C (68°F to 88°F)
    Heat 10°C to 30°C (48°F to 88°F)
    Dual Setpoint Auto Same as the above range, but there are temperatures that cannot be set due to the deadband.
    Auto 18°C to 30°C (64°F to 88°F) or 20°C to 30°C (68°F to 88°F)
    The lower limit of the settable temperature differs by the place of use.
    T
    he heating set temperature range of 10°C to 15°C (48°F to 58°F) may not be settable, depending on the indoor unit model.
  • Deadband:
    The deadband is the minimum value of the difference between the set temperature for cooling and the set temperature for heating (= cooling set temperature - heating set temperature) in Dual Setpoint Auto mode.
    The difference between the set temperature for cooling and heating in Dual Setpoint Auto mode cannot be smaller than the deadband.
    The deadband is set in the indoor unit.
    To change this, consult authorized service personnel.