Perform the setting change or removal for Zone (B)

Zone setting screen (B)

(a) Schedule setting
Day of the week and period can be specified at Schedule setting.
Operate (b) to (z) by this function.

Item Max. number of registration
Schedule 4 (per 1 zone)
Program 12 (per 1 schedule)

NOTES:

  • When Start/Stop, operation mode setting, room temp. setting, fan speed setting, airflow direction setting, swing setting, economy mode, and anti-freeze setting are changed frequently by using the central controller like BMS, System controller, Touch panel controller, etc., the number of operations for each indoor unit must not exceed 7,500 times/year.
    If the number of setting change exceeds the above specified number, the rewriting frequency of the EEPROM (built into the air conditioner and used for setting memory) will be exceeded and may cause breakdown.
  • If it is determined that the setting of cooling set temperature and heating set temperature is out of deadband value, the operation setting will not be sent.
  • When multiple users operate this system at the same time, more items than the above table can be registered.
    If you use this system with such a condition, we do not guarantee the proper operation of the AIRSTAGE Cloud Edge Supervisor and the connected device.

(b) Link button

  • Add Schedule
    Adds schedule.

(c) [-+] button
Expands or collapses the display.

(1) [Today] button
Displays week or month containing today's date.

(2) [<] button
Displays previous week or month.  

(3) [>] button
Displays next week or month.

(4) Week / Month selection button
Selects any week or month.

(5) [Week / Month] button
Selects weekly display or monthly display.

(6) Schedule visualizer
Displays the setting schedule visually.  

  • For Week

    (7) When schedule or exception is set, it is displayed at the top of the screen.
    (8) The set program is displayed until the start time of the next program setting.
    In the above example, on a weekday, there is a program at 8:00 every morning, from Monday to Friday. Since there is another program at 8:00 on Saturday and Sunday, the weekday program is displayed until 8:00 on Saturday.

  • For Month

    When schedule or exception is set, it is displayed on the setting date.  
    (9) The program in the schedule is displayed until the end date, so it is displayed overlapping with the next program start date.

(d) Displays the setting schedule name and period.

(e) Schedule Timer icon
When the Schedule execution period comes, the icon turns green.

(f) Schedule [On/Off]
Sets On/Off for the setting Schedule.

(g) Link button

  • Delete Schedule
    Select this to delete existing Schedule.
  • Add Program
    Select this to add new Program.  

    NOTE: If a Program is being edited, save it before performing “Add Program”.
    When “Add Program” is performed, the changes by the currently editing Program are cancelled.

(h)  Enter the schedule name.

(i) Enter the start date of the schedule.

(j) Enter the end date of the schedule.

(k) [SAVE] button
Saves the schedule.

(l) The setting Program name and period are displayed.

(m) Program [On/Off]
Sets On/Off for the setting Program.

(n) Link button

  • Delete Program
    Select this to delete existing Program.

(o) Select the day of the week.

(p) Enter the program name.

(q) Enter the start time of the program.
The indoor units start/stop at the time.
For details, refer to "Example of Schedule".

(u) Auto Off [On/Off] icon
On/Off of Auto Off and time can be set.

NOTE: If Auto Off Timer is On, when the set time elapses after any indoor unit gets into operating state in the Zone, all indoor units are automatically stopped in the Zone.
If the indoor unit operating state is changed during countdown of Auto Off Timer, the time of countdown is reset.

(v) [SAVE] button
Saves the schedule.

(w) Link button

  • Add Function
    Select this to add new Zone Function.

(x) Link button

  • Remove
    Select this to delete existing Zone Function.

(y) Set the temperature setpoint.

  • Dual Setpoint Auto:
    Set the set temperature for cooling and the set temperature for heating separately. During the Dual Setpoint Auto mode operation, when the room temperature exceeds the set temperature for cooling, the cooling operation is performed, and when the room temperature falls below the set temperature for heating, the heating operation is performed. (It can be used only when the setting of the indoor unit compatible with this function is valid.)
  • The settable temperature range is different for each operation mode.
    Settable temperature range
    Cool/Dry* 18 to 30 °C (64 to 88 °F) or 20 to 30 °C (68 to 88 °F)
    Heat 10 to 30 °C (48 to 88 °F)
    Dual Setpoint Auto Same as the above range, but there are temperatures that cannot be set due to the deadband.
    Auto* 18 to 30 °C (64 to 88 °F) or 20 to 30 °C (68 to 88 °F)
    The lower limit of the setting temperature is different depending on the place of use.
    The heating set temperature range of 10°C to 15°C (48°F to 58°F) may not be settable, depending on the indoor unit model.
  • Deadband:
    The deadband is the minimum value of the difference between the set temperature for cooling and the set temperature for heating (= cooling set temperature - heating set temperature) in Dual Setpoint Auto mode.
    The difference between the set temperature for cooling and heating in Dual Setpoint Auto mode cannot be smaller than the deadband. The deadband is set in the indoor unit. To change this, consult authorized service personnel.

(z) Set the operation mode.

NOTE: When the operation mode is set while its setting is limited, it is not reflected in the indoor unit even if saved. If the changed setting is not reflected in the operation mode, confirm that the operation mode is active.

(10) Set the thermal On/Off
Sets On/Off for the device that can set temperature registered in the Zone.

(11) Link button

  • Remove
    Select this to delete existing Zone Function.

(12) Set the Ventilation On/Off
Sets On/Off for the device that can set ventilation registered in the Zone.

(13) Ventilation Target Temperature
Sets the target temperature of fresh air supplied to the Zone by Ventilator.

(14) Target airflow volume
Sets the target airflow volume.

(15) Ventilator Operation Mode
Sets the operation mode.

"Add Schedule" window

(a) Enter the schedule name.

(b) Enter the start date.

(c) Enter the end date.

(d) [Cancel] button

(e) [Save] button
Saves the Schedule.

"Add Zone Functions" window

(a) Select the Zone function to be added.

(b) [CANCEL] button

(c) [ADD] button
Adds the Zone functions.