Change the setting of Edge Supervisor

Start-up
  1. Select the button (a) on Site Dashboard screen.

"Edge Supervisor Settings" window
  1. Enter the following page information.
  2. To complete the setting, select the button (i).
    The setting will be saved, and the window will close.

If you want to close the window without saving the changes, select the button (h).

(a) [RESTART] button
Reboots the AIRSTAGE Cloud Edge Supervisor at the Site.

(b) DHCP

(c) IP Address

Network setting of AIRSTAGE Cloud Edge Supervisor is displayed.

(d) Gateway Address

Network setting of AIRSTAGE Cloud Edge Supervisor is displayed.

(e) Netmask

(f)  Network setting of AIRSTAGE Cloud Edge Supervisor is displayed. (Supported in the future)

When set to "On", AIRSTAGE Cloud Edge Supervisor becomes the WLAN access point (AP), and web application can be operated using PC or tablet. AP name is the 14-digit number in SSID#1.

(g) External Input

"Emergency Stop" or "All ON/OFF" can be used by signal input to the AIRSTAGE Cloud Edge Supervisor .

  • In case of AIRSTAGE Edge Controller: For the usage method, refer to the installation manual.
  • In case of PE100A (UTY-DSGXZ*): Set the following three items and use them.
    • "Use External input": To use the External Input function, set to "On".
    • "Detection Method": Set this item according to the table below.
    • "Action" : Set this item according to the table below.

      Detection Method

      Port Input signal Action
      Edge DI1 Low → High "Emergency Stop" or "All on"
      High → Low "Emergency Stop" reset or "All on"
      Pulse

      DI1 Low → High "Emergency Stop" or "All on"
      DI2 Low → High "Emergency Stop" reset or "All on"

NOTE:

  • "Detection Method" and "Action" functions use the DI1 and DI2 ports on the PE100A.  For the electrical characteristics and connection methods, refer to the PE100A installation manual.
  • When "Action" is set to "Emergency Stop", VRF system is Emergency Stop.