Medium Static Pressure Duct (Compact Size) ARXG22KHTAP / AOYG22KBTB
Features
- Highly efficient and quiet operation
- Small and lightweight outdoor unit
- Automatic airflow adjustment
- Low ambient operation
Capacity
6.0 kW
7.0 kW
Specification
Power source | Phase | Single-phase | |
---|---|---|---|
Voltage | 230 V | ||
Frequency | 50 Hz | ||
EGAT | Capacity | Cooling | 21000 (3100 - 22900) BTU/h |
SEER | 21.5 BTU/h | ||
Rank | 5 ★★ | ||
Capacity | Cooling | 6.0 (0.9 - 6.7) kW | |
Heating | 7.0 (0.9 - 8.0) kW | ||
Input Power | Cooling | 1.710 kW | |
Heating | 1.810 kW | ||
EER | Cooling | 3.51 W/W | |
COP | Heating | 3.87 W/W | |
Pdesign | Cooling | 6.0 kW | |
Heating (-10°C) | 4.8 kW | ||
SEER | Cooling | ||
SCOP | Heating (Average) | 4.20 W/W | |
Energy Efficiency Class | Cooling | A++ | |
Heating (Average) | A+ | ||
Starting Current | 8.2 A | ||
Max. Operating Current | Cooling | 12.60 A | |
Heating | 12.60 A | ||
Annual Energy Consumption | Cooling | 323 kWh/a | |
Heating | 1597 kWh/a | ||
Moisture Removal | 1.50 l/h | ||
Sound Pressure Level*2 | Indoor (Cooling) | High | 28 dB(A) |
Middle | 25 dB(A) | ||
Low | 22 dB(A) | ||
Quiet | 20 dB(A) | ||
Indoor (Heating) | High | 28 dB(A) | |
Middle | 25 dB(A) | ||
Low | 22 dB(A) | ||
Quiet | 20 dB(A) | ||
Sound Pressure Level*2 | Outdoor (Cooling) | High | 51 dB(A) |
Outdoor (Heating) | High | 51 dB(A) | |
Sound Power Level | Indoor (Cooling) | High | 57 dB(A) |
Indoor (Heating) | High | 57 dB(A) | |
Outdoor (Cooling) | High | 63 dB(A) | |
Outdoor (Heating) | High | 63 dB(A) | |
Air Flow Rate | Indoor (Cooling) | High | 1050 m³/h |
Outdoor (Cooling) | High | 2240 m³/h | |
Static pressure range (Standard) | 30 - 200 (35) Pa | ||
Net Dimensions Indoor |
Height | 300 mm | |
Width | 1000 mm | ||
Depth | 700 mm | ||
Net Dimensions Outdoor |
Height | 632 mm | |
Width | 799 mm | ||
Depth | 290 mm | ||
Net Weight | Indoor | 35.0 kg | |
Outdoor | 38.0 kg | ||
Connection Pipe Diameter | Liquid | φ6.35 mm | |
Gas | φ12.7 mm | ||
Drain Hose Diameter | φ25(I.D.), φ32(O.D.) mm | ||
Max Pipe Length (Pre Charge) | 30.0 (20.0) m | ||
Max Height Difference | 25 m | ||
Operation Range | Cooling | -15 to 46 °CDB | |
Heating | -15 to 24 °CDB | ||
Refrigerant | Type | R32 | |
Global Warming Potential | 675 | ||
Charge | 1250 g (0.844 CO2eq–T) |
Scroll
- *2.
- The noise value is the value when measured in an anechoic room. When measured in the actual installed state,surrounding noise and reflections are received and the measured value is usually larger than the indicated value.