Specification
Power source | Phase | 3-phase | |
---|---|---|---|
Voltage | 230 V | ||
Frequency | 50 Hz | ||
Capacity | Cooling | 19.0 kW(8.4 - 20.9) kW | Heating | 22.4 kW (7.2 - 24.6) kW |
Input Power | Cooling | 6.46 kW | |
Heating | 6.59 kW | ||
EER | Cooling | 2.94 W/W | |
COP | Heating | 3.4 W/W | |
Max. Operating Current | Cooling | 4.6 A | |
Heating | 4.6 A | ||
Moisture Removal | 4.5 I/h | ||
Sound Pressure Level*2 | Indoor (Cooling) | High | 46 dB(A) |
Middle | 43 dB(A) | ||
Low | 41 dB(A) | ||
Quiet | 39 dB(A) | ||
Indoor (Heating) | High | 46 dB(A) | |
Middle | 43 dB(A) | ||
Low | 41 dB(A) | ||
Quiet | 39 dB(A) | ||
Sound Pressure Level*2 | Outdoor (Cooling) | High | 55 dB(A) |
Outdoor (Heating) | High | 55 dB(A) | |
Air Flow Rate | Indoor | High | 4300 m3/h |
Outdoor | High | 8400 m3/h | |
Static pressure range (Standard) | 50 to 150 (72) Pa | ||
Net Dimensions Indoor |
Height | 360 mm | |
Width | 1400 mm | ||
Depth | 850 mm | ||
Net Dimensions Outdoor |
Height | 1428 mm | |
Width | 1080 mm | ||
Depth | 480 mm | ||
Net Weight | Indoor | 69 kg (152 lbs) | |
Outdoor | 165 kg (363 lbs) | ||
Connection Pipe Diameter | Liquid | 12.7 mm | |
Gas | 25.4 mm | ||
Drain Hose Diameter | Indoor | 23.4 mm | |
Outdoor | 25.4 mm | ||
Max Pipe Length (Pre Charge) | 100 (30) m | ||
Max Height Difference | 30 m | ||
Operation Range | Cooling | -15 to 46 °CDB | |
Heating | -20 to 24 °CDB | ||
Refrigerant | Type | R410A | |
Global Warming Potential | 2,088 | ||
Charge | 5,600 g |
Scroll
- *2.
- The noise value is the value when measured in an anechoic room. When measured in the actual installed state,surrounding noise and reflections are received and the measured value is usually larger than the indicated value.