Heat Pump Modular Type V-III Series AJY342LALBHH  [3Phase]

Outdoor unit

Outdoor Unit :
AJY126LALBH
Outdoor Unit :
AJY108LALBH
Outdoor Unit :
AJY108LALBH
Download :
Catalogue

Features

  • Excellent energy saving
  • Great design flexibility for placement in any building
  • Easy installation and maintenance
  • Outstanding efficiency in real-world operating conditions
  • Energy-saving technologies for boosting operational efficiency

Capacity

Cooling  107.0 kW
Heating  120.0 kW


Specification

Rated Capacity Range 38
Maximum Connectable Indoor Unit 64
Indoor unit connectable capacity 53.5 - 160.5 kW
Scroll
Power source Phase 3-phase 4 wire
Voltage 400 V
Frequency 50 Hz
Capacity Cooling 107.0 kW
Heating 120.0 kW
Input Power Cooling 28.88 kW
Heating 28.47 kW
EER Cooling 3.70 W/W
COP Heating 4.21 W/W
Air Flow Rate 13,000×3 m³/h
Sound Pressure Level*2 Cooling 64 dB(A)
Heating 65 dB(A)
Sound Power Level Cooling 84 dB(A)
Heating 88 dB(A)
Max. External Static Pressure 82 Pa
Compressor Motor Output 11.0×3 kW
Heat exchanger fin Blue fin
Net Dimensions Height 1,690 mm
Width 1,240×3 mm
Depth 765 mm
Net Weight 275×3 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 11.8×3 kg
Connection Pipe Diameter Liquid 19.05 mm
Gas 41.27 mm
Operation Range Cooling -5 to 46 °CDB
Heating -20 to 21 °CDB
Scroll
Note:
Specifications are based on the following conditions.
Cooling:
Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating:
Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length:
7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
When cooling operation will be conducted at outdoor air temperature below -5°C,
the outdoor unit must be installed in a position that is higher than or equal to those of indoor units.
*1
Minimum connectable indoor unit number is 2.
*2
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
surrounding noise and reflections are received and the measured value is usually larger than the indicated value.

Dimensions

Outdoor Unit : AJY126LALBH / AJY108LALBH / AJY108LALBH

Outdoor unit