Heat Pump for Small Capacity Type J-IIS Series AJY045LCLAH
Features
- Small and lightweight outdoor units
- Advanced technologies for high efficiency
- Long piping length
- Nonstop operation during oil recovery
- Easy installation
Capacity
14.0 kW
16.0 kW
Specification
Rated Capacity Range | 5 |
---|---|
Maximum Connectable Indoor Unit | 8 |
Scroll
Power source | Phase | Single-phase |
---|---|---|
Voltage | ~230 V | |
Frequency | 50 Hz | |
Capacity | Cooling | 14.0 kW |
Heating | 16.0 kW | |
Input Power | Cooling | 4.43 kW |
Heating | 3.93 kW | |
EER | Cooling | 3.16 W/W |
COP | Heating | 4.07 W/W |
Air Flow Rate | 4,200 m³/h | |
Sound Pressure Level*2 | Cooling | 53 dB(A) |
Heating | 55 dB(A) | |
Sound Power Level | Cooling | 69 dB(A) |
Heating | 69 dB(A) | |
Heat exchanger fin | Blue fin | |
Net Dimensions | Height | 998 mm |
Width | 970 mm | |
Depth | 370 mm | |
Net Weight | 86 kg | |
Refrigerant | Type | R410A |
Global Warming Potential | 2,088 | |
Charge | 4.0 kg | |
Connection Pipe Diameter | Liquid | 9.52 mm |
Gas | 15.88 mm | |
Total pipe length | 80 m | |
Max. height difference | 30 m | |
Operation Range | Cooling | -5 to 46 °CDB |
Heating | -20 to 21 °CDB |
Scroll
- Note:
- Specifications are based on the following conditions.
- Cooling:
- Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
- Heating:
- Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
- Pipe length:
- 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
- The protective function may work when using it outside the operation range.