Heat Pump Modular type V-III TROPICAL Series AJY342LNTCH
- Outdoor Unit :
- AJY162LNTCH
- Outdoor Unit :
- AJY090LNTCH
- Outdoor Unit :
- AJY090LNTCH
- Download :
- Catalogues
Features
- Excellent energy saving
- Great design flexibility for placement in any building
- Easy installation and maintenance
- Energy-saving technologies for boosting operational efficiency
- Thorough anti-corrosion treatment
- Outstanding cooling capacity
Specification
Rated Capacity Range | 38 HP |
---|---|
Maximum Connectable Indoor Unit | 2 - 55 |
Indoor unit connectable capacity | 53.0 - 137.8 kW |
Scroll
Power source | Phase | 3-phase |
---|---|---|
Voltage | 380-415(50Hz),400(60Hz) V | |
Frequency | 50/60 Hz | |
Capacity | Cooling | 106.0 kW |
Heating | 113.0 kW | |
Input Power | Cooling | 31.12 kW |
Heating | 28.13 kW | |
EER | Cooling | 3.41 W/W |
COP | Heating | 4.02 W/W |
Air Flow Rate | 13700 + 11100 + 11100 m³/h | |
Sound Pressure Level*2 | Cooling | 65 dB(A) |
Heating | 66 dB(A) | |
Max. External Static Pressure | 82 Pa | |
Compressor Motor Output | 11 x 1 + 7.5 x 1 + 7.5 x 1 kW | |
Heat exchanger fin | Blue fin | |
Net Dimensions Height X Width X Depth |
1690 x 1240 x 765 mm
1690 x 930 x 765 mm 1690 x 930 x 765 mm |
|
Net Weight |
279 kg
255 kg 255 kg |
|
Refrigerant | Type | R410A |
Charge |
11.8 kg
11.7 kg 11.7 kg |
|
Connection Pipe Diameter | Liquid | φ19.05 mm |
Gas | φ41.27 mm | |
Max. height difference (Outdoor Unit: Upper/Lower) |
50 / 40 m | |
Operation Range | Cooling | -5 to 52 °CDB |
Heating | -20 to 21 °CDB |
Scroll
- Note:
- Specifications are based on the following conditions.
- Cooling:
- Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
- Heating:
- Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
- Pipe length:
- 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
- *1
- Minimum connectable indoor unit number is 2.
- *2
- The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
- surrounding noise and reflections are received and the measured value is usually larger than the indicated value.