High Static Pressure Duct ARXC36GATH

Indoor unit

Indoor Unit :
ARXC36GATH
Download :
Catalogue

Capacity

Cooling  11.2 kW
Heating  12.5 kW


Specification

Power source Phase Single-phase
Voltage ~230 V
Frequency 50 Hz
Capacity Cooling 11.2 kW
Heating 12.5 kW
Input Power 207 W
Air Flow Rate High 1,990 m3/h
Middle 1,680 m3/h
Low 1,330 m3/h
Static Pressure Range 0 to 200 Pa
Standard Static Pressure 100 Pa
Sound Pressure Level*2 High 42 dB(A)
Middle 36 dB(A)
Low 32 dB(A)
Net Dimensions Height 400 mm
Width 1,050 mm
Depth 500 mm
Net Weight 40 kg (88 lbs)
Connection Pipe Diameter Liquid (Flare) 9.52 (Flare) mm
Gas (Flare) 19.05 (Flare) mm
Drain Hose Diameter Indoor 25 mm
Outdoor 32 mm
Scroll
Note:
Specifications are based on the following conditions.
Cooling:
Indoor temperature of 27˚CDB / 19˚CWB, and outdoor temperature of 35˚CDB / 24˚CWB.
Heating:
Indoor temperature of 20˚CDB / (15˚CWB), and outdoor temperature of 7˚CDB / 6˚CWB.
Pipe length:
7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
Voltage:
230 [V].

Dimensions

Indoor Unit : ARXC36GATH

Indoor unit