One-way Flow Cassette AUXV024GLEH

Indoor unit

Indoor Unit :
AUXV024GLEH
Download :
Catalogues

Capacity

Cooling   7.1 kW
Heating   8.0 kW


Specification

Power source Phase Single-phase
Voltage 230 V
Frequency 50 Hz
Capacity Cooling 7.1 kW
Heating 8.0 kW
Input Power 99 W
Air Flow Rate Cooling High 1150 m³/h
Medium High 1020 m³/h
Middle 940 m³/h
Low High 790 m³/h
Low 700 m³/h
Quiet 610 m³/h
Heating High 1150 m³/h
Medium High 1020 m³/h
Middle 940 m³/h
Low High 790 m³/h
Low 700 m³/h
Quiet 610 m³/h
Sound Pressure Level*2 Cooling High 49 dB(A)
Medium High 47 dB(A)
Middle 45 dB(A)
Low High 42 dB(A)
Low 39 dB(A)
Quiet 36 dB(A)
Heating High 49 dB(A)
Medium High 47 dB(A)
Middle 45 dB(A)
Low High 42 dB(A)
Low 39 dB(A)
Quiet 36 dB(A)
Net Dimensions Height 198 mm
Width 1190 mm
Depth 570 mm
Net Weight 27.0 kg
Connection Pipe Diameter Liquid (Flare) φ9.52 mm
Gas (Flare) φ15.88 mm
Drain Hose Diameter φ25(I.D.), φ32(O.D.) mm
EV Kit (optional) EV Kit (optional)
Scroll
*2.
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,surrounding noise and reflections are received and the measured value is usually larger than the indicated value.