Heat Pump for Small Capacity Type J-IIS Series AJY054LCLAH

Outdoor unit

Outdoor Unit :
AJY054LCLAH
Download :
Catalogue

Features

  • Small and lightweight outdoor units
  • Advanced technologies for high efficiency
  • Long piping length
  • Nonstop operation during oil recovery
  • Easy installation

Capacity

Cooling  15.1 kW
Heating  16.5 kW


Specification

Rated Capacity Range 6
Maximum Connectable Indoor Unit 8
Scroll
Power source Phase Single-phase
Voltage ~230 V
Frequency 50 Hz
Capacity Cooling 15.1 kW
Heating 16.5 kW
Input Power Cooling 5.03 kW
Heating 4.11 kW
EER Cooling 3.00 W/W
COP Heating 4.01 W/W
Air Flow Rate 4,200 m³/h
Sound Pressure Level*2 Cooling 54 dB(A)
Heating 56 dB(A)
Sound Power Level Cooling 70 dB(A)
Heating 70 dB(A)
Heat exchanger fin Blue fin
Net Dimensions Height 998 mm
Width 970 mm
Depth 370 mm
Net Weight 87 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 4.0 kg
Connection Pipe Diameter Liquid 9.52 mm
Gas 15.88 mm
Total pipe length 80 m
Max. height difference 30 m
Operation Range Cooling -5 to 46 °CDB
Heating -20 to 21 °CDB
Scroll
Note:
Specifications are based on the following conditions.
Cooling:
Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating:
Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length:
7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
The protective function may work when using it outside the operation range.

Dimensions

Outdoor Unit : AJY054LCLAH

Outdoor unit