Heat Pump Modular type V-III TROPICAL Series AJY234LNLBHH [3Phase]

- Outdoor Unit :
- AJY090LNLBH
- Outdoor Unit :
- AJY072LNLBH
- Outdoor Unit :
- AJY072LNLBH
- Download :
-
Catalogue
Features
- Excellent energy saving
- Great design flexibility for placement in any building
- Easy installation and maintenance
- Energy-saving technologies for boosting operational efficiency
- Thorough anti-corrosion treatment
- Outstanding cooling capacity
Capacity


Specification
Rated Capacity Range | 26 |
---|---|
Maximum Connectable Indoor Unit | 43 |
Indoor unit connectable capacity | 36.4 - 94.6 kW |
Scroll
Power source | Phase | 3-phase |
---|---|---|
Voltage | ~400 V | |
Frequency | 50,60 Hz | |
Capacity | Cooling | 72.8 kW |
Heating | 81.5 kW | |
Input Power | Cooling | 17.68 kW |
Heating | 17.59 kW | |
EER | Cooling | 4.12 W/W |
COP | Heating | 4.63 W/W |
Air Flow Rate | 11100×3 m³/h | |
Sound Pressure Level | Cooling | 62 dB(A) |
Heating | 63 dB(A) | |
Sound Power Level | Cooling | 83 dB(A) |
Heating | 85 dB(A) | |
Max. External Static Pressure | 82 Pa | |
Compressor Motor Output | 7.5×3 kW | |
Heat exchanger fin | Blue fin | |
Net Dimensions | Height | 1690×3 mm |
Width | 930×3 mm | |
Depth | 765×3 mm | |
Net Weight | 255×3 kg | |
Refrigerant | Type | R410A |
Global Warming Potential | 2,088 | |
Charge | 11.7×3 kg | |
Connection Pipe Diameter | Liquid | 15.88 mm |
Gas | 34.92 mm | |
Operation Range | Cooling | -5 to 46 °CDB |
Heating | -20 to 21 °CDB |
Scroll
- Note:
- Specifications are based on the following conditions.
- Cooling:
- Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
- Heating:
- Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
- Pipe length:
- 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
- *1
- Minimum connectable indoor unit number is 2.
- *2
- The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
- surrounding noise and reflections are received and the measured value is usually larger than the indicated value.