Heat Pump Modular type V-III TROPICAL Series AJY144LNLBHH  [3Phase]

Outdoor unit

Outdoor Unit :
AJY072LNLBH
Outdoor Unit :
AJY072LNLBH
Download :
Catalogue

Features

  • Excellent energy saving
  • Great design flexibility for placement in any building
  • Easy installation and maintenance
  • Energy-saving technologies for boosting operational efficiency
  • Thorough anti-corrosion treatment
  • Outstanding cooling capacity

Capacity

Cooling  44.8 kW
Heating  50.0 kW

Specification

Rated Capacity Range 16
Maximum Connectable Indoor Unit 26
Indoor unit connectable capacity 22.4 - 58.2 kW
Scroll
Power source Phase 3-phase
Voltage ~400 V
Frequency 50,60 Hz
Capacity Cooling 44.8 kW
Heating 50.0 kW
Input Power Cooling 10.40 kW
Heating 10.34 kW
EER Cooling 4.31 W/W
COP Heating 4.84 W/W
Air Flow Rate 11100×2 m³/h
Sound Pressure Level Cooling 59 dB(A)
Heating 61 dB(A)
Sound Power Level Cooling 80 dB(A)
Heating 83 dB(A)
Max. External Static Pressure 82 Pa
Compressor Motor Output 7.5×2 kW
Heat exchanger fin Blue fin
Net Dimensions Height 1690 mm
Width 930×2 mm
Depth 765 mm
Net Weight 279×2 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 11.7×2 kg
Connection Pipe Diameter Liquid 12.70 mm
Gas 28.58 mm
Operation Range Cooling -5 to 46 °CDB
Heating -20 to 21 °CDB
Scroll
Note:
Specifications are based on the following conditions.
Cooling:
Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating:
Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length:
7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
*1
Minimum connectable indoor unit number is 2.
*2
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
surrounding noise and reflections are received and the measured value is usually larger than the indicated value.