Medium Static Pressure Duct (Compact Size) ARXG18KHTAP

Indoor unit, Remote controller, Outdoor unit

ALL DC
Indoor Unit :
ARXG18KHTAP
Outdoor Unit :
AOEG18KBTB
Download :
Catalogues

Features

  • Highly efficient and quiet operation
  • Small and lightweight outdoor unit
  • Automatic airflow adjustment
  • Low ambient operation

Feature Icons

Economy mode: A thermostat setting is adjusted automatically according to the room temperature to avoid unnecessary cooling or heating. Setting temperature range limitation: Sets the minimum and maximum limits on room temperature to establish the right balance between energy saving and a comfortable environment. Set temperature auto return: The setting temperature automatically returns to the previously set temperature. Auto changeover: The unit automatically switches between heating and cooling modes based on the temperature setting and the room temperature. Automatic fan speed: A micro-computer automatically adjusts the airflow to follow the changes in room temperature. Auto restart: In the event of a temporary power failure, the air conditioner will automatically restart in the same operating mode as before, once the power supply is restored. Connectable fresh air duct: Outside air can be introduced by attaching a locally purchased duct to the fresh air knockout and an optional part. Auto-off timer: Automatically stops operation when a fixed time has elapsed from the start of operation. Weekly timer: Different ON-OFF times can be set for each day. Filter sign: Indicates the filter cleaning period by blinking. External ON/OFF input Special Cooling: Special Cooling Automatic airflow adjustment: Automatically detects required airflow in each application case and adjusts the volume. Drain pump equipped as standard Blue fin

Capacity

Cooling   5.2 kW
Heating   6.0 kW


Specifications

Power Source Phase Single phase
Voltage 230 V
Frequency 50 Hz
Capacity Cooling 5.2 (0.9 - 5.9) kW
Heating 6.0 (0.9 - 7.5) kW
Input Power Cooling 1.360 kW
Heating 1.560 kW
EER Cooling 3.82 W/W
COP Heating 3.85 W/W
Pdesign Cooling 5.2 kW
Heating (-10°C) 4.4 kW
SEER Cooling 6.50 W/W
SCOP Heating (Average) 4.10 W/W
Energy Efficiency Class Cooling A++
Heating (Average) A+
Max. Operating Current Cooling 12.10 A
Heating 12.10 A
Annual Energy Consumption Cooling 280 kWh/a
Heating 1501 kWh/a
Moisture Removal 1.20 l/h
Sound Pressure Level*2 Indoor (Cooling) High 28 dB(A)
Middle 25 dB(A)
Low 22 dB(A)
Quiet 20 dB(A)
Indoor (Heating) High 28 dB(A)
Middle 25 dB(A)
Low 22 dB(A)
Quiet 20 dB(A)
Sound Pressure Level*2 Outdoor (Cooling) High 50 dB(A)
Outdoor (Heating) High 50 dB(A)
Sound Power Level Indoor (Cooling) High 54 dB(A)
Indoor (Heating) High 54 dB(A)
Outdoor (Cooling) High 62 dB(A)
Outdoor (Heating) High 62 dB(A)
Airflow Rate Indoor (Cooling) High 1050 m³/h
Outdoor (Cooling) High 2160 m³/h
Static Pressure Range (standard) 30 - 200 (35) Pa
Net Dimensions
Indoor
Height 300 mm
Width 1000 mm
Depth 700 mm
Net Dimensions
Outdoor
Height 632 mm
Width 799 mm
Depth 290 mm
Net Weight Indoor 35.0 kg
Outdoor 36.0 kg
Connection Pipe Diameter Liquid φ6.35 mm
Gas φ12.7 mm
Drain Hose Diameter φ25(I.D.), φ32(O.D.) mm
Max. Pipe Length (Pre Charge) 30.0 (20.0) m
Max. Height Difference 20 m
Operation Range Cooling -15 to 46 °C DB
Heating -15 to 24 °C DB
Refrigerant Type R32
Global Warming Potential 675
Charge 1020 g (0.689 CO2eq–T)
Scroll

Dimensions

Indoor Unit : ARXG18KHTAP

Indoor unit