Medium Static Pressure Duct (Standard) ARXG45KMLA  [3Phase]

Indoor unit, Remote controller, Outdoor unit

ALL DC
Indoor Unit :
ARXG45KMLA
Outdoor Unit :
AOEG45KRTA
Download :
Catalogues

Features

  • Slim and compact design
  • Easy maintenance
  • Drain pipe can be installed on either the left or right side of the unit
  • Low ambient operation across classes

Feature Icons

Economy mode: A thermostat setting is adjusted automatically according to the room temperature to avoid unnecessary cooling or heating. Auto changeover: The unit automatically switches between heating and cooling modes based on the temperature setting and the room temperature. Automatic fan speed: A micro-computer automatically adjusts the airflow to follow the changes in room temperature. Auto restart: In the event of a temporary power failure, the air conditioner will automatically restart in the same operating mode as before, once the power supply is restored. Connectable fresh air duct: Outside air can be introduced by attaching a locally purchased duct to the fresh air knockout and an optional part. Connectable distributing duct: Locally purchased branch ducts can be attached to the systems to distribute the airflow. Weekly & Temperature setback timer: Weekly & Temperature setback timer can set the temperature for 2-time spans and for each day of the week. Filter sign: Indicates the filter cleaning period by blinking. Blue fin

Capacity

Cooling   12.1 kW
Heating   13.5 kW


Specifications

Power Source Phase 3 phase 3N
Voltage 400 V
Frequency 50 Hz
Capacity Cooling 12.1 (4.0 - 13.0) kW
Heating 13.5 (4.2 - 15.2) kW
Input Power Cooling 4.220 kW
Heating 3.840 kW
EER Cooling 2.87 W/W
COP Heating 3.52 W/W
Max. Operating Current Cooling 14.0 A
Heating 14.0 A
Moisture Removal 4.0 l/h
Sound Pressure Level*2 Indoor (Cooling) High 42 dB(A)
Middle 38 dB(A)
Low 32 dB(A)
Quiet 28 dB(A)
Indoor (Heating) High 42 dB(A)
Middle 38 dB(A)
Low 32 dB(A)
Quiet 28 dB(A)
Sound Pressure Level*2 Outdoor (Cooling) High 57 dB(A)
Outdoor (Heating) High 57 dB(A)
Sound Power Level Indoor (Cooling) High 68 dB(A)
Indoor (Heating) High 70 dB(A)
Outdoor (Cooling) High 71 dB(A)
Outdoor (Heating) High 71 dB(A)
Airflow Rate Indoor (Cooling) High 2100 m³/h
Outdoor (Cooling) High 4450 m³/h
Static Pressure Range (standard) 30 - 150 (60) Pa
Net Dimensions
Indoor
Height 270 mm
Width 1135 mm
Depth 700 mm
Net Dimensions
Outdoor
Height 998 mm
Width 940 mm
Depth 320 mm
Net Weight Indoor 39.0 kg
Outdoor 67 kg
Connection Pipe Diameter Liquid φ9.52 mm
Gas φ15.88 mm
Max. Pipe Length (Pre Charge) 50 (30.0) m
Max. Height Difference 30 m
Operation Range Cooling -15 to 46 °C DB
Heating -15 to 24 °C DB
Refrigerant Type R32
Global Warming Potential 675
Charge 2700 g (1.823 CO2eq–T)
Scroll

Dimensions

Indoor Unit : ARXG45KMLA