Medium Static Pressure Duct (Compact Size) ARXG30KHTAP
Features
- Highly efficient and quiet operation
- Small and lightweight outdoor unit
- Automatic airflow adjustment
- Low ambient operation
Capacity
8.5 kW
10.0 kW
Specifications
Power Source | Phase | Single phase | |
---|---|---|---|
Voltage | 230 V | ||
Frequency | 50 Hz | ||
Capacity | Cooling | 8.5 (2.8 - 10.0) kW | |
Heating | 10.0 (2.7 - 11.2) kW | ||
Input Power | Cooling | 2.650 kW | |
Heating | 2.630 kW | ||
EER | Cooling | 3.21 W/W | |
COP | Heating | 3.80 W/W | |
Pdesign | Cooling | 8.5 kW | |
Heating (-10°C) | 8.0 kW | ||
SEER | Cooling | 6.23 W/W | |
SCOP | Heating (Average) | 4.00 W/W | |
Energy Efficiency Class | Cooling | A++ | |
Heating (Average) | A+ | ||
Max. Operating Current | Cooling | 22.60 A | |
Heating | 22.60 A | ||
Annual Energy Consumption | Cooling | 477 kWh/a | |
Heating | 2796 kWh/a | ||
Moisture Removal | 2.30 l/h | ||
Sound Pressure Level*2 | Indoor (Cooling) | High | 36 dB(A) |
Middle | 33 dB(A) | ||
Low | 30 dB(A) | ||
Quiet | 29 dB(A) | ||
Indoor (Heating) | High | 36 dB(A) | |
Middle | 33 dB(A) | ||
Low | 30 dB(A) | ||
Quiet | 29 dB(A) | ||
Sound Pressure Level*2 | Outdoor (Cooling) | High | 53 dB(A) |
Outdoor (Heating) | High | 55 dB(A) | |
Sound Power Level | Indoor (Cooling) | High | 63 dB(A) |
Indoor (Heating) | High | 65 dB(A) | |
Outdoor (Cooling) | High | 68 dB(A) | |
Outdoor (Heating) | High | 69 dB(A) | |
Airflow Rate | Indoor (Cooling) | High | 1700 m³/h |
Outdoor (Cooling) | High | 3750 m³/h | |
Static Pressure Range (standard) | 30 - 200 (47) Pa | ||
Net Dimensions Indoor |
Height | 300 mm | |
Width | 1000 mm | ||
Depth | 700 mm | ||
Net Dimensions Outdoor |
Height | 788 mm | |
Width | 940 mm | ||
Depth | 320 mm | ||
Net Weight | Indoor | 36.0 kg | |
Outdoor | 52.0 kg | ||
Connection Pipe Diameter | Liquid | φ9.52 mm | |
Gas | φ15.88 mm | ||
Drain Hose Diameter | φ25(I.D.), φ32(O.D.) mm | ||
Max. Pipe Length (Pre Charge) | 50.0 (30.0) m | ||
Max. Height Difference | 30 m | ||
Operation Range | Cooling | -15 to 46 °C DB | |
Heating | -15 to 24 °C DB | ||
Refrigerant | Type | R32 | |
Global Warming Potential | 675 | ||
Charge | 1900 g (1.283 CO2eq–T) |
Scroll
- *2.
- The noise value is the value when measured in an anechoic room. When measured in the actual installed state,surrounding noise and reflections are received and the measured value is usually larger than the indicated value.