Outdoor Air Unit ARXH054GTAH

ERV ARXH054GTAHT

Outdoor Air Unit :
ARXH054GTAH
Download :
Catalogue

Features

  • One VRF system can provide air conditioning and air supply at the same time
  • High energy savings and flexible duct design by using DC motor
  • Top class compact design
  • Various Controller

Production by order


Specification

Power source Phase Single-phase
Voltage ~ 230 V
Frequency 50 Hz
Capacity Cooling 14.0 kW
Heating 8.9 kW
Input Power Cooling 179/179 W
Heating 179/179 W
Air Flow Rate 1080 m³ /h
Static Pressure Standard 185 Pa
Range 50 - 185 Pa
Sound Pressure Level 42 dB(A)
Net Dimensions Height 425 mm
Width 1367 mm
Depth 572 mm
Net Weight 48 kg
Connection Pipe Diameter Small Φ9.52 mm
Large Φ19.05 mm
Operation Range Cooling 5 to 43 °CDB
Heating -7 to 21 °CDB
Refrigerant Type R410A
Scroll
Note :
Specifications are based on the following conditions.
Cooling :
Outdoor temperature of 33 °CDB / 28 °CWB.
Heating :
Outdoor temperature of 0 °CDB / -2.9 °CWB.
Pipe length :
7.5 m
Voltage :
230 [ V ].

Dimensions

Outdoor Air Unit : ARXH054GTAH

Outdoor Air Unit - Dimensions