Low Static Pressure Duct
ARXB18GALH
Feature
- Low noise level
- Compact design
- Two-direction drain piping
- 2 way air-intake
- Flexible installation
Specification
Indoor Unit : ARXB18GALH
Power source | 230V,1Φ, 50Hz |
---|---|
Capacity | Cooling 5.6kW Heating 6.3kW |
Input power | 96W |
Air flow late | High 890m³/h Med 810m³/h Low 730m³/h |
Static pressure range | 0 to 50Pa |
Standard static pressure | 25Pa |
Sound pressure level | High 36dB(A) Med 34dB(A) Low 30dB(A) |
Dimensions | 217(H) × 953(W) × 595(D)mm |
Weight | 23kg |
Connection pipe diameter | Liquid (Flare) Φ9.52mm Gas (Flare) Φ15.88mm Drain hose VP25 [Φ25 (I.D) ; Φ32 (O.D.)]mm |
- Note :
- Specifications are based on the following conditions.
- Cooling :
- Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
- Heating :
- Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
- Pipe length :
- 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
- Voltage :
- 230 [V].
Dimensions
- *
- Service accessibility must be allowed for when installing the product.
Please consult the installation manual for the necessary service access size.