HRV/ERV Solutions VS3000 RTe
![](/shared/us/img-fcus-vrf-ventacity-vs3000-rte-01.png)
- Download :
-
Catalog
Dimensions
![](/shared/us/img-fcus-vrf-ventacity-vs3000rte-dimensions-01.jpg)
Parts
![](/shared/us/img-fcus-vrf-ventacity-vs3000rte-parts-01.jpg)
Feature
Port Configurations
![](/shared/us/img-fcus-vrf-ventacity-vs3000rt-port-configurations-01.jpg)
Accessories
- Room CO2 Sensor*
- Duct CO2 Sensor*
- Smart Building Gateway
- *
- Only one per ventilator
PERFORMANCE
![](/shared/us/img-fcus-vrf-ventacity-vs500-sq-icon1-01.png)
Exceptional energy efficiency performance puts the VS3000 RTe in a class by itself.
![](/shared/us/img-fcus-vrf-ventacity-vs500-sq-icon2-01.png)
With its polymer counterflow heat exchanger core, the VS3000 RTe transfers 72-87% of the heat and 51-82% of the moisture between fresh and exhaust air streams.
![](/shared/us/img-fcus-vrf-ventacity-vs500-sq-icon3-01.png)
Our fans incorporate electronically commutated motors (ECMs) and backward curving fan blades, reducing the power required for air movement.
FAN OPERATING RANGE
![](/shared/us/img-fcus-vrf-ventacity-vs3000rte-fan-operating-range-01.jpg)
FAN VOLUME & POWER RANGE
Ext. Static Pressure (in. W.C.) |
1.3 | 1.5 | 1.8 | 2.5 | 3 |
---|---|---|---|---|---|
Maximum Flow (CFM) | 3,300 | 3,200 | 3,000 | 2,500 | 2,000 |
System Power (Watts) | 3,871 | 3,916 | 3,884 | 3,766 | 3,474 |
Scroll
LATENT EFFICIENCY
![](/shared/us/img-fcus-vrf-ventacity-vs3000rte-latent-efficiency-01.jpg)
SENSIBLE EFFICIENCY
![](/shared/us/img-fcus-vrf-ventacity-vs3000rte-sensible-efficiency-01.jpg)
TOTAL EFFICIENCY
![](/shared/us/img-fcus-vrf-ventacity-vs3000rte-total-efficiency-01.jpg)
Specifications
Ventilation Flow-Nominal | 3,300 cfm |
---|---|
Ventilation Flow – Typical | 750 to 3,000 cfm |
Ventilation Type | Energy Recovery Ventilator (ERV) |
Heat Exchanger | Counterflow Polymer Static Plate |
Fan Type | Backward Curved, Centrifugal, EC |
Heat Recovery – Max | Sensible – 87% Latent – 82% Total – 85% |
Temperature Range | -13° F to 122° F |
Humidity – Inside Max | 90% RH |
Operation Modes | CAV, DCV, VAV, BMS, Economizer |
Duct Connection | 22” Dia (380 in2) Min. |
Discharge Air Temperature Control | Continuously Variable Bypass |
Mechanical
Weight | 1,720 lbs |
---|---|
Shipping Weight | 2,186 lbs |
Dimensions | 86.3” L x 48.3” W x 73.5” H |
Shipping Dimensions | 92” L x 59” W x 83” H |
OA PreFilter (Actual Size) | 51” x 26.5” x 1.75” MERV6 |
OA Filter (Actual Size) | 51” x 26.5” x 3.75” MERV13 |
RA Filter (Actual Size) | 51” x 25.25” x 3.75” MERV8 |
Base Anchor Dimension | 36.8” x 73.7” |
External Finish | Powder Coat Over Galvanized Steel |
Electrical
Power Supply | 208 VAC | 480 VAC** |
---|---|---|
Phase | 3Φ | 3Φ |
Power Supply | 20.2 kW | 25.6 kW |
FLA – Max | 56 A | 36.8 A |
MCA | 68.6 A | 44.6 A |
MOP | 70 A | 60 A |
De-Ice Preheater | 16.3 kW | 21.7 kW |
Fan Motor Type | EC | |
Maximum Power per Fan | 1.9 kW (2.56 hp) |
- **
- Unit is supplied 480V power and must have a field supplied step-down transformer (required) for the internal electronic controls which operate at 208V.