HRV/ERV Solutions VS1000 RT
![](/shared/us/img-fcus-vrf-ventacity-vs1000-rt-01.png)
- Download :
-
Catalog
Dimensions
![](/shared/us/img-fcus-vrf-ventacity-vs1000-rt-dimensions-01.jpg)
Parts
![](/shared/us/img-fcus-vrf-ventacity-vs1000-rt-parts-01.jpg)
Feature
FAN VOLUME
Ext. Static Pressure (in. W.C.) | 0.25 | 0.5 | 0.75 | 1 | 1.25 | 1.5 | 1.75 |
---|---|---|---|---|---|---|---|
Maximum Flow (CFM) | 1,060 | 1,060 | 1,000 | 970 | 970 | 830 | 735 |
System Power (Watts) | 790 | 878 | 918 | 906 | 888 | 878 | 859 |
Scroll
FAN POWER*
Air Flow (CFM) | 175 | 200 | 400 | 600 | 800 | 1,000 | 1,060 |
---|---|---|---|---|---|---|---|
CFM / WATT (2 Fans) | 3.5 | 3.6 | 4.3 | 3.3 | 2.2 | 1.6 | 1.5 |
System Power (Watts) | 66 | 72 | 109 | 198 | 380 | 640 | 723 |
Scroll
- *
- at 1/8" water column
PERFORMANCE
![](/shared/us/img-fcus-vrf-ventacity-vs500-sq-icon1-01.png)
Exceptional energy efficiency performance puts the VS1000 RT in a class by itself.
![](/shared/us/img-fcus-vrf-ventacity-vs500-sq-icon2-01.png)
With its aluminum counterflow heat exchanger core, the VS1000 RT transfers 82% to 93% of the heat between fresh and exhaust air streams.
![](/shared/us/img-fcus-vrf-ventacity-vs500-sq-icon3-01.png)
Our fans incorporate electronically commutated motors (ECMs) and backward curving fan blades, reducing the power required for air movement.
FAN OPERATING RANGE
![](/shared/us/img-fcus-vrf-ventacity-vs1000-rt-specific-fan-operating-range-01.jpg)
HEAT RECOVERY EFFICIENCY
![](/shared/us/img-fcus-vrf-ventacity-vs1000-rt-heat-recovery-efficiency-01.jpg)
PORT CONFIGURATIONS
![](/shared/us/img-fcus-vrf-ventacity-vs1000-rt-port-configurations-01.jpg)
ACCESSORIES
- Room CO2 Sensor
- Duct CO2 Sensor
- Room RH Sensor
- VOC Sensor
- Smart Building Gateway
Specifications
Ventilation Flow – Max | 1,060 cfm |
---|---|
Ventilation Flow – Typical | 75 to 1,000 cfm |
Ventilation Type | Heat Recovery Ventilator (HRV) |
Heat Exchanger | Counterflow Aluminum Static Plate |
Fan Type | Backward Curved, Centrifugal, EC |
Heat Recovery – Max | 93% |
Temperature Range | -13° F to 140° F |
Humidity – Inside Max | 90% RH |
Operation Modes | CAV, DCV, VAV, BMS, Economizer |
Noise – Max | 52.6 dBA |
NRTL Test Specifications | UL1812, CSA C22.2 No. 113 |
Duct Connection (Room Air, Supply Air) |
None |
Duct Connection (Outside Air, Exhaust Air) |
14" Dia. (154 in2) Min. |
Temperature Control | Continuously Variable Bypass |
MECHANICAL
Weight | 616 lbs |
---|---|
Shipping Weight | 845 lbs |
Dimensions | 63.6" L x 35.2" W x 52.5" H |
Shipping Dimensions | 74" L x 45" W x 51" H |
OA Filter (Actual Size) | 17.5" L x 24.5" W x 3.75" H MERV13 |
RA Filter (Actual Size) | 16.5" L x 24.5" W x 1.75" H MERV8 |
Base Anchor Dimension | 26.3" x 52.8" |
External Finish | Powder Coat Over Galvanized Steel |
ELECTRICAL
Power Supply | 6.9 kW |
---|---|
Voltage | 240 VAC 1Φ, 208/240 VAC 3Φ, 60Hz |
FLA – Max | 30 A (1Φ) |
De-Ice Preheater | 6.0 kW |
Fan Motor Type | EC |
Maximum Power – 1 Fan | 485W (.65hp) |