Heat Pump for Small Capacity Type J-IIIL Series AJY126LELAH

Outdoor unit

Outdoor Unit :
AJY126LELAH
Download :
Catalogue

Features

  • Compact Design
  • Advanced high efficiency technology
  • Long Piping Length
  • Top class indoor unit connection
  • High Static Pressure
  • Top Class Low Operating Sound

Capacity

Cooling  40.0 kW
Heating  40.0 kW


Specification

Rating Capacity Range 14
Maximum Connectable Indoor Unit*1 1 - 36
Scroll
Power source Phase 3 phase
Voltage ~400 V
Frequency 50 Hz
Capacity Cooling 40.0 kW
Heating 40.0 kW
Input Power Cooling 12.12 kW
Heating 9.71 kW
EER Cooling 3.30 W/W
COP Heating 4 .12 W/W
Air Flow Rate 13,000 m/³h
Sound Pressure Level*2 Cooling 62 dB(A)
Heating 63 dB(A)
Net Dimensions Height 1,638 mm
Width 1,080 mm
Depth 480 mm
Net Weight 213 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 11.0 (22.9) kg
Connection Pipe Diameter Liquid 12.70 mm
Gas 28.58 mm
Operation Range Cooling -5 to 46 °CDB
Heating -20 to 21 °CDB
Scroll
Note:
Specifications are based on the following conditions.
Cooling:
Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating:
Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
*
The cooling operation range of -15 to 46°C is allowed only when all of the indoor units connected to the system are higher than capacity of 5.6kW.
Pipe length:
7.5 m; Height difference between outdoor unit and indoor unit : 0 m.