Heat Recovery Modular Type VR-II Series AJYA72GALH  [3phase]

Outdoor unit

Outdoor Unit :
AJYA72GALH
Download:
Catalogue

Features

  • System Outline
  • High Operating Energy Efficiency
  • Energy saving technology that boosted operation efficiency
  • Ideal heat exchanger path control
  • Sophisticated operation control
  • Flexible piping connection
  • Flexible installation of RB unit

Capacity

Cooling  22.4 kW
Heating  25.0 kW

Specification
Rating Capacity range 8
Maximum Connectable Indoor Unit*1 15
Indoor unit connectable capacity 11.2 - 33.6 kW
Scroll
Power source Phase 3-phase 4 wire
Voltage 400 V
Frequency 50 Hz
Capacity Cooling 22.4 kW
Heating 25.0 kW
Input Power Cooling 5.45 kW
Heating 5.70 kW
EER Cooling 4.11 W/W
COP Heating 4.39 W/W
Air flow late 11,100 m/³h
Sound pressure level*2 Cooling 56 dB(A)
Heating 58 dB(A)
Sound power level Cooling 77 dB(A)
Heating 80 dB(A)
Maximum external static pressure 80 Pa
Compresor motor output 7.5 kW
Heat exchanger fin Blue fin
Net Dimension Height 1,690 mm
Width 930 mm
Depth 765 mm
Net Weight Indoor 262 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 11.8 kg
Connection pipe
diameter
Liquid 12.70 mm
Discharge Gas 15.88 mm
Suction Gas 22.22 mm
Operation range Cooling -10 to 46 °CDB
Heating -20 to 21 °CDB
Cooling / Heating -10 to 21 °CDB
Scroll
*1
Minimum connectable indoor unit number is 2.
*2
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
surrounding noise and reflections are received and the measured value is usually larger than the indicated value.
Dimensions

Outdoor Unit : AJYA72GALH

Outdoor unit