Heat Recovery Modular Type VR-II Series AJY432GALH  [3phase]

Outdoor unit

Outdoor Unit :
AJY144GALH
Outdoor Unit :
AJY144GALH
Outdoor Unit :
AJY144GALH
Download:
Catalogue

Features

  • System Outline
  • High Operating Energy Efficiency
  • Energy saving technology that boosted operation efficiency
  • Ideal heat exchanger path control
  • Sophisticated operation control
  • Flexible piping connection
  • Flexible installation of RB unit

Capacity

Cooling  135.0 kW
Heating  150.0 kW


Specification
Rating Capacity range 48
Maximum Connectable Indoor Unit*1 64
Indoor unit connectable capacity 67.5 - 202.5 kW
Scroll
Power source Phase 3-phase 4 wire
Voltage 400 V
Frequency 50 Hz
Capacity Cooling 135.0 kW
Heating 150.0 kW
Input Power Cooling 40.83 kW
Heating 38.31 kW
EER Cooling 3.31 W/W
COP Heating 3.92 W/W
Air flow late 13,000×3 m/³h
Sound pressure level*2 Cooling 66 dB(A)
Heating 66 dB(A)
Sound power level Cooling 87 dB(A)
Heating 88 dB(A)
Maximum external static pressure 80 Pa
Compresor motor output 11.0×3 kW
Heat exchanger fin Blue fin
Net Dimension Height 1,690 mm
Width 1,240×3 mm
Depth 765 mm
Net Weight Indoor 286×3 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 11.8×3 kg
Connection pipe
diameter
Liquid 19.05 mm
Discharge Gas 34.92 mm
Suction Gas 41.27 mm
Operation range Cooling -10 to 46 °CDB
Heating -20 to 21 °CDB
Cooling / Heating -10 to 21 °CDB
Scroll
*1
Minimum connectable indoor unit number is 2.
*2
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
surrounding noise and reflections are received and the measured value is usually larger than the indicated value.
Dimensions

Outdoor Unit : AJY144GALH / AJY144GALH / AJY144GALH

Outdoor unit