Heat Pump for Small Capacity Type J-IIS Series AJY040LCLAH

Outdoor unit

Outdoor Unit :
AJY040LCLAH
Download :
Catalogue

Features

  • Small and light weight outdoor unit
  • Advanced high efficiency technology
  • Long piping length
  • Non-stop oil recovery operation
  • Easier Installation

Capacity

Cooling  12.1 kW
Heating  13.6 kW

Specification

Rating Capacity Range 4
Maximum Connectable Indoor Unit*1 7
Scroll
Power source Phase Single-phase
Voltage ~230 V
Frequency 50 Hz
Capacity Cooling 12.1 kW
Heating 13.6 kW
Input Power Cooling 3.44 kW
Heating 3.09 kW
EER Cooling 3.52 W/W
COP Heating 4.40 W/W
Air Flow Rate 4,040 m/³h
Sound Pressure Level*2 Cooling 51 dB(A)
Heating 54 dB(A)
Sound Power Level Cooling 67 dB(A)
Heating 68 dB(A)
Heat exchanger fin Blue fin
Net Dimensions Height 998 mm
Width 970 mm
Depth 370 mm
Net Weight Indoor 86 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 4.0 kg
Connection Pipe Diameter Liquid 9.52 mm
Gas 15.88 mm
Operation Range Cooling -5 to 46 °CDB
Heating -20 to 21 °CDB
Scroll
Note:
Specifications are based on the following conditions.
Cooling:
Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating:
Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length:
7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
The protective function may work when using it outside the operation range.

Dimensions

Outdoor Unit : AJY040LCLAH

Outdoor unit