AIRSTAGE™  (VRF Systems)

Rating Capacity range 4HP

AJYA40LALH

Outdoor units


 

Specifications

Rating Capacity range 4HP
Maximum Connectable Indoor Unit 7
Power source Single-phase, ~230V, 50Hz
Capacity Cooling  12.1kW  Heating 13.6kW
Input power Cooling  3.25kW  Heating 3.17kW
EER Cooling  3.72W/W
COP Heating  4.29W/W
Air flow late 6,200m³/h
Sound pressure level Cooling  50dB(A)  Heating 52dB(A)
Heat exchanger fin Blue fin
Dimensions 1,334(H) × 970(W) × 370(D)mm
Weight 117kg
Refrigerant charge 4.8kg
Connection pipe diameter Liquid φ9.52mm
Gas φ15.88mm
Operation range Cooling  -5 to 46°CDB
Heating -20 to 21°CDB
Note :
Specifications are based on the following conditions.
Cooling :
Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating :
Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length :
7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
The protective function may work when using it outside the operation range.

Dimensions

Outdoor Dimensions : 1,334(H) × 970(W) × 370(D)mm


 

Top of Page


Related Links

Downloads

Contact