Slim Concealed Floor ARXD09GALH

Indoor unit

Indoor Unit :
ARXD09GALH
Download :
Catalogue

Capacity

Cooling  2.8 kW
Heating  3.2 kW

Specification

Power source Phase Single-phase
Voltage ~230 V
Frequency 50 Hz
Capacity Cooling 2.8 kW
Heating 3.2 kW
Input Power 50 W
Air Flow Rate High 600 m3/h
Middle 550 m3/h
Low 480 m3/h
Static pressure range 0 to 90 Pa
Standard static pressure 25 Pa
Sound Pressure Level High 29 dB(A)
Middle 26 dB(A)
Low 24 dB(A)
Net Dimensions Height 198 mm
Width 700 mm
Depth 620 mm
Net Weight 17 kg (37 lbs)
Connection Pipe Diameter Liquid (Flare) 6.35 mm
Gas (Flare) 12.70 mm
Drain Hose Diameter Indoor 25 mm
Outdoor 32 mm
Scroll
Note:
Specifications are based on the following conditions.
Cooling:
Indoor temperature of 27˚CDB / 19˚CWB, and outdoor temperature of 35˚CDB / 24˚CWB.
Heating:
Indoor temperature of 20˚CDB / (15˚CWB), and outdoor temperature of 7˚CDB / 6˚CWB.
Pipe length:
7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
Voltage:
230 [V].

Dimensions

Indoor Unit : ARXD09GALH

Indoor unit