Energy Recovery Ventilator UTZ-BD080B

ERV UTZ-BD080BT

Energy Recovery Ventilator :
UTZ-BD080B
Download :
Catalogue

Features

  • Energy efficiency and ecology
  • Features of heat exchange element
  • Quiet operation
  • Extended range of an external static pressure
  • Slim shape and easier installation
  • Reverse mountable direct air supply / exhaust system

Specification

Rated flow rate 800 m³ /h
Power source 220 - 240 V
50 Hz
Heat Exchange Ventilation Input Power (Extra Hhigh) 418 W
High 378 W
Low 295 W
Air Flow Rate (Extra Hhigh) 800 m³ /h
High 800 m³ /h
Low 630 m³ /h
External static pressure (Extra Hhigh) 140 Pa
High 110 Pa
Low 55 Pa
Temperature Exchange Efficiency (Extra Hhigh) 75 %
High 75 %
Low 76 %
External static pressure Cooling (Extra Hhigh) 65 %
High 65 %
Low 68 %
External static pressure Heat pump (Extra Hhigh) 71 %
High 71 %
Low 74 %
Sound Pressure Level (Extra Hhigh) 37.5 dB*
High 37 dB*
Low 34.5 dB*
Normal Ventilation Input Power (Extra Hhigh) 418 W
High 378 W
Low 295 W
Air Flow Rate (Extra Hhigh) 800 m³ /h
High 800 m³ /h
Low 630 m³ /h
External static pressure (Extra Hhigh) 140 Pa
High 110 Pa
Low 55 Pa
Sound Pressure Level (Extra Hhigh) 37.5 dB*
High 37 dB*
Low 34.5 dB*
Net Dimensions Height 1322 mm
Width 884 mm
Depth 388 mm
Net Weight 71 kg
Outlet duct diameter 250 mm
Operation Range -10 to 40 °C
Maximum humidity 85 %
Scroll
*
The noise level must be measured 1.5 m below the centre of the unit.

Dimensions

Energy Recovery Ventilator : UTZ-BD080B

Energy recovery ventilator unit - Dimensions